Skip to main content

Fire Alarm Panel Guide

Foothills Unitarian Church  |  Facilities  |  Last updated: June 2026

Overview

Foothills Unitarian Church uses a Honeywell E3 fire alarm control panel. This guide explains the system layout, how to respond to an alarm, how to silence the panel, and how to coordinate with our fire safety vendor and monitoring company.

 

System Components & Locations

Fire Alarm Control Panel

        Location: Admin Lobby, to the left as you enter through the wooden doors

        Make/Model: Honeywell E3

        The panel displays system status ("System Normal"), time, and date at all times

        A System Record Documents box is mounted below the panel

        A strobe/horn is mounted above the panel

        One fire extinguisher is mounted on the wall to the right of the panel

EwirQMGQJ9MtvC47-embedded-image-rei7zmcy.jpeg

 

Monitoring Communication Hardware

        Location: Cleaning closet next to the kitchen

        Includes a Honeywell Power Supply unit and AES IntelliNet cellular communicator

        This hardware contacts the monitoring company automatically when an alarm is triggered

S26gMSiDWOptC3bd-embedded-image-jrxclbqa.jpeg

 

Riser Room (Sprinkler System)

        Location: Chalice Wing Basement, across from the elevator

        Contains the sprinkler system risers and backflow devices

 

Fire Extinguishers

        There are 12 fire extinguishers located throughout the building

        One is located in the Admin Lobby next to the fire alarm panel

        All extinguishers are inspected annually in February

 

Monitoring Company

CES – Commercial Electronic Systems

Website: www.electronicssystems.com

        Phone: 720-755-3826

        Account #: AED240A

        Monitoring Center (24/7): 1-800-432-1429

mAxd3f5JfvhlDUa4-embedded-image-ld4c8yfw.jpeg

 

For actual fires or serious alarms, the monitoring center will automatically dispatch the fire department and then call the contacts below in order until someone answers. Each person must provide their password to acknowledge the alarm.

 

Alarm Notification Call List:

1.     Holly Ayala – Facilities Coordinator – 970-342-1118 – Password: 7469

2.     Katie Watkins – Director of Operations and Finance – 970-658-6728 – Password: 2410

3.     Jenn Powell – Event and Operations Manager – 970-829-1068 – Password: 2020

If the first person does not answer, the monitoring center will call the next person on the list until someone responds.

 

Alarms Website (myalarms.com): Use this to put the system into test mode so the fire department is NOT dispatched during planned testing or inspections.

        Website: myalarms.com

        Username: FHFacilities

        Password: stored in Dashlane

 

Fire Safety Vendor – National Fire and Safety

Website: www.natfiresafety.com

NFS handles all annual inspections and service calls under a 2-year contract (through end of 2028).

 

Key Contacts:

        Todd Harrison – Sales/Account Rep: c. 720-428-9534 | tharrison@frontierfireprotection.com

        Alex DePesa – Service Coordinator: (303) 629-0221 ext 106 | direct: (303) 285-2050 | adepesa@natfiresafety.com

        Natalie Mondragon – Service Coordinator: (303) 629-0221 x 127

 

Inspection Schedule:

        February – Annual fire alarm, sprinkler, and fire extinguisher inspections

        June – Annual backflow inspections (reports submitted to the City of Fort Collins)

 

Service Calls:

        For any fire alarm or sprinkler issues, contact NFS directly

        Hourly service rates: $175/hr (fire alarm) | $235/hr (sprinkler)

 

Step-by-Step Instructions

Step 1: Check the Panel Status

The panel display shows the current system status at all times. Check this first before taking any action.

        "System Normal" – no action needed

        "Alarm" – follow the alarm response steps below

        "Trouble" – contact NFS for service

        "Supervisory" – contact NFS for service

aD5ML0hYXFsZR0ul-embedded-image-dv18ar6n.jpeg

 

Step 2: Responding to an Alarm

If the alarm sounds:

4.     Call 911 immediately if there is any sign of fire or smoke.

5.     Evacuate the building following posted evacuation routes.

6.     Go to the fire alarm panel in the Admin Lobby.

7.     Press Alarm Acknowledge to silence the notification and identify the alarm zone on the display.

8.     Press Signal Silence to stop the audible alarm while you investigate.

9.     Once the situation is confirmed safe and the cause is resolved, press System Reset / Lamp Test to restore the system to normal.

10.  Call the CES Monitoring Center at 1-800-432-1429 to confirm the alarm status and advise whether a fire department response is needed.

 

Step 3: Before a Scheduled Inspection or Test

To prevent the fire department from being dispatched during a planned inspection:

11.  Log in to myalarms.com with username FHFacilities (password in Dashlane).

12.  Put the system into test mode.

13.  Notify NFS that the system is in test mode and they may proceed.

14.  When the inspection is complete, take the system out of test mode on myalarms.com.

15.  Confirm with NFS that all systems are restored to normal.

 

Step 4: Making a Building-Wide Announcement

The fire panel includes a PA system with zone control buttons and a handset microphone.

16.  Locate the handset inside the panel (lower compartment).

bOE15laJwNKP302P-embedded-image-pcwhl12w.jpeg

17.  Press the zone button for the area you want to reach (All Call, HVAC, Elevator, Sanctuary A/V, etc.).

a55g6WEvaRZdC3us-embedded-image-liexmxjs.jpeg

18.  Speak clearly into the handset.

 

Troubleshooting

Problem: Panel shows "Trouble" but no alarm is sounding

Fix: Do not attempt to clear a Trouble condition yourself. Contact NFS at (303) 629-0221 to schedule a service call.

 

Problem: Alarm triggered accidentally (no fire or smoke)

Fix: Press Alarm Acknowledge, then Signal Silence. Call the CES Monitoring Center at 1-800-432-1429 to advise it was a false alarm. Press System Reset to restore the panel. If the fire department was already dispatched, meet them at the entrance and explain the situation.

 

Problem: Panel will not reset after an alarm

Fix: The underlying alarm condition must be cleared before the panel will reset. Ensure all doors, pull stations, and smoke detectors are back to normal. If the panel still will not reset, call NFS.

 

Problem: Fire department was called during a planned inspection

Fix: Meet them at the entrance and explain that a scheduled inspection was in progress. In the future, log in to myalarms.com before any inspection to place the system in test mode.

 

Problem: AES communicator in the cleaning closet has a fault light

Fix: Contact CES at 720-755-3826 (Account #AED240A) to report the issue. Also notify NFS so they are aware monitoring may be impaired.

 

FAQs

Q: Who do I call first in a real fire – 911 or the monitoring company?

Always call 911 first. The monitoring company will also be notified automatically by the AES communicator, but your first call should be to emergency services.

Q: What happens if I don’t answer when CES calls during an alarm?

The monitoring center will move on to the next person on the call list. If no one answers, they will rely on the fire department response. Make sure your password (7469 for Holly, 2410 for Katie, 2020 for Jenn) is memorized so you can quickly acknowledge the call.

Q: How often is the fire alarm system inspected?

The fire alarm, sprinkler, and fire extinguishers are inspected annually every February. Backflow devices are inspected annually every June. All inspections are handled by National Fire and Safety.

Q: What is the System Record Documents box below the panel?

It contains the official inspection reports and system documentation required to be kept on site for the local Authority Having Jurisdiction (AHJ). Do not remove documents from this box.

Q: Can staff silence or reset the panel themselves?

Yes, staff can acknowledge and silence the alarm using the panel buttons. Always call the CES Monitoring Center after silencing to confirm the system status. If the situation is unclear or the panel cannot be reset, call NFS for service.

Q: What zones does the PA system cover?

The panel PA buttons include: All Call, Notification & Door Holders, Elevator, HVAC, and Sanctuary A/V. Additional unlabeled buttons may correspond to other zones – check with NFS for a full zone map.

Q: What if we need to add or change a fire extinguisher location?

Contact NFS at (303) 629-0221. They handle all fire extinguisher service and placement under the maintenance contract.